Three phase lightning protection module(Type A) HD-D380M-A

    Online Inquiry
    Click Refresh Verification Code

    Details

    Power supply lightning protection moduletype A

    Electric surge protector of low-voltage distribution system is design according to IEC standard.It has invalidation detection indication,standard modularization installation,changeable lightning protection module and powerful discharge capacity of lightning current.It’s appliable to the protection of buildings’ general supply system against lightning.With 35mm standard guide-way,this lightning arrester is very convenient to be maintained.It connects with the circuit in parallel and has no limit to the power of equipment fixed later.


    Model

    HD-D380M40A

    HD-D380M20A

    Nominal working voltage Un

    380V

    380V

    Maximum continuous working voltage Uc

    385V

    385V

    Nominal discharge current In8/20ms

    20KA

    10KA

    Maximum discharging current Imax8/20ms

    45KA

    20KA

    Voltage protection level Up

    1.6KV

    1.2KV

    Dimension

    72×66×90mm

    Response time Ta

    ≤25ns

    Operating temperature range Tup

    -40℃至+70℃

    Section of minimum installed conductor

    6mm2Multi-folded wire

    Protection grade

    IP20

    Sheathing material

    Flame retardant thermoplastic material

    Mode of connection

    Parallel connection

    Protection mode

    4+0/3+1/2+0/1+1


    Installation:

    Ground the null line repeatedly when Long-distance overhead incoming lines enter buildings.

    Plug the power phase line (L) and null line (Ninto corresponding connector of the electric surge protector and make sure it's firm and reliable. Connect the ground terminal of arrester with the ground lead of lightning protection well (recommended earth resistance 4Ω).

    Suggested specification of the lead wire: no less than 6mm2, short and straight.


    Home
    Tel
    Message
    Contact