    Data line lightning protection module

    This product is suitable for the protection of Monitor platform, decoding lines, access control data lines, background music, video intercom, intelligent three meters, a wide-used card and fire alarm circuits.It can prevent the damage of line induction overvoltage equipment due to earth potential increase and has low output residual voltage,little insertion loss and double overcurrent protection.


    MODEL

    HD-XC

    Nominal working voltage Un

    24V

    Maximum continuous working voltage Uc

    32V

    Nominal discharge current In 8/20μs

    5KA

    Maximum discharging current Imax8/20μs

    10KA

    Voltage protection level Up

    X-X

    150V

    (X-G)

    350V

    External dimension

    113*50*38mm

    Response time Ta

    0.1ns

    Operating temperature range Tup

    -40 to +70

    Insertion loss

    0.2dB

    Insertion resistance

    4Ω

    Protection grade

    IP30

    Sheathing material

    Shielding plastic fire-proof material

    Application

    Data line

    Interface mode

    Terminal


    Put an arrester in series at the leading end of the line interface of the protected equipment.”OUT” is equipment end and “IN” is incoming line end.Connect the arrester ground terminal and lightning protection ground lead well (suggested earth resistance4Ω)