Composite lightning protection Box(Type B+C) HD-D380/220B-XL

    Online Inquiry
    Click Refresh Verification Code

    Details

    Power supply lightning protection series

    Electric surge protector of composite low-voltage distribution system, which is in the form of a box, is designed according to IEC standard. It adopts the most advanced technology of preignition clearance and automatic matching of energy and has validation detection indication, overflowing and overheating protection, lightning stroke numbering display and powerful discharge capacity of lightning current. It can be used in Grade B and C lightning protection for the general supply of building, machine room, plant and enterprise to make sure the safe operation of electronic equipment and other utilization equipment. This lightning arrester is very convenient to be maintained. It connects with the circuit in parallel and has no limit to the power of equipment fixed later.



    MODEL

    HD-D380220BC-XL200

    HD- D380220BC-XL100

    HD- D380220BC-XL60

    HD-D380/220B-XL

    Nominal working voltage Un

    380/220V

    380/220V

    380/220V

    380/220V

    Maximum continuous working voltage Uc

    385/275V

    385/275V

    385/275V

    385/275V

    Nominal discharge current In8/20μs

    200KA

    100KA

    60KA

    10KA

    Voltage protection level Up

    2KV

    1.5KV

    1KV

    2.5KV

    Response time Ta

    100ns

    Operating temperature range Tup

    -40to+70

    Working condition indication

    Green light means work normally,red light means fault indicaiton.

    Section of minimum installed conductor

    6mm2 multi-folded wire

    Protection grade

    IP20

    External dimension

    280*350*130mm

    Sheathing material

    Metal spraying

    Mode of connection

    parallel connection

    Protection mode

    4+0/3+1/1+1/2+0





















    Ground the null line repeatedly when Long-distance overhead incoming lines enter buildings.

    Plug the power phase line (L) and null line (Ninto corresponding connector of the electric surge protector and make sure it's firm and reliable. Connect the ground terminal of arrester with the ground lead of lightning protection well (recommended earth resistance4Ω).

    Suggested specification of the lead wire: no less than 6mm2, short and straight.