HD-D220M20C

    Online Inquiry
    Click Refresh Verification Code

    Details

    Series connection type power surge protector

    This product adopts ultra-fast conduction of large-capacity surge absorbing element "zinc oxide varistor" as the core component, with normal or failure indication function, and installed over-current thermal tripping mechanism, in case of failure can be automatically detached from the grid. Meets electrical safety standards.

    With a variety of shapes of power outlets, it is suitable for all electrical equipment that meets national standards.



    Model

    HD-D220M20C

    Nominal working voltage Un

    220V

    Maximum continuous working voltage Uc

    275V

    Nominal discharge current In8/20μs

    10KA

    Maximum discharging current Imax8/20μs

    20KA

    Voltage protection level Up

    1.2KV

    Response time Ta

    25ns

    Over-current protection

    10A

    Fault indication

    Yes

    Protection grade

    IP40

    External dimension

    98*50*38mm

    Sheathing material

    Flame retardant thermoplastic material

    Mode of connection

    In Series


    Installation method:

    When the plug of the lightning protection socket is plugged into the mains jack, please make sure that the mains line is normal and the power line (L) and neutral line (N) have no errors.. You can connect the plug of the lightning protection socket to mains jack to ensure the reliability.

    When a long-distance overhead line enters a building, the neutral line is grounded repeatedly, and the grounded end of the connection socket or lightning protection ground wire is connected well.

    (Recommended grounding resistance ≤ 4Ω)